The combination of ventilated floor is similar to that of the antistatic all steel floor in structure,but its enclosed space is of no foarming filler.
There are punched vents on the upper and lower steel plates of the floor as well as on the veneer.The ventilated floor used with the all-steel access floor is applicable to the sites with ventilaftion requirements for the undermeath of loor.The ventilation rate of floor is 20%~45%.
Product Detail

The combination of ventilated floor is similar to that of the antistatic all steel floor in structure,but its enclosed space is of no foarming filler.

There are punched vents on the upper and lower steel plates of the floor as well as on the veneer.The ventilated floor used with the all-steel access floor is applicable to the sites with ventilaftion requirements for the undermeath of loor.The ventilation rate of floor is 20%~45%.


typeSizeφmm x Pcs

Ventilation

Rate

CONCENTRATED LOAD

(deflection=2mm)

Ultimate LoadUniform LoadFlatnessVertical
lbNkg
AS450-TFA600×600φ8 x 153622%≥450≥1960≥200≥5880≥9720≤0.6mm≤0.3mm
AS800-TFB600×600φ16 x 57632%≥800≥3550≥360≥10700≥17000
AS800-TFC600×600φ22 x 40042%
AS1000-TFD600×600φ10 x 91820%≥1000≥4450≥450≥13350≥23000
AS1000-TFE600×600φ(52 x 18) x 12845%